Pump Control Panel RFQ Checklist for EPC Buyers

EPC procurementMotor and pump controlPublished

For a pump control panel RFQ, specify the operating duty before naming the starter. A soft starter can suit a fixed-speed pump that needs a controlled start. A variable frequency drive (VFD) is a candidate when the process needs speed control during operation. For two pumps, also specify when the second unit should take over, whether both can run together and what happens after power returns. Those decisions affect the power circuit, protection, control logic and test scope.

This checklist is for ordinary industrial process and water-service pumps. Use the project designer's approved requirements for fire pumps and other safety-critical services.

Choose the operating duty before the starting method

  • Fixed-speed duty. Ask the electrical and mechanical designers to confirm the starting conditions, permissible current, acceleration and stopping behaviour. A soft starter changes how a motor starts and, on suitable equipment, stops. In normal running the motor operates on line-frequency power. Confirm the pump and pipework limits rather than assuming a smooth ramp alone will solve a hydraulic problem.
  • Variable-speed duty. Identify the controlled variable, such as discharge pressure, and provide the pump curve, required operating range, motor data and sensor arrangement. Ask the supplier to declare the proposed drive and any necessary motor, cable, ventilation or filtering provisions. The designer should confirm the permissible speed range and the behaviour when feedback is invalid.
  • Two-pump duty. State whether the second pump replaces the first on failure, assists at high demand or can perform both duties under separately defined conditions. Specify whether lead selection is fixed, alternates on an agreed event or is changed by an operator. If both can run, ask the designer to confirm the simultaneous electrical and hydraulic duty.

Specify what “bypass” means

A soft-starter bypass contactor may carry current after normal acceleration and take the starter's semiconductors out of the running path. A drive bypass is a separately designed alternative power path for the same motor. If that path connects the motor directly to line power, variable-speed control is unavailable in that mode. Confirm that full-speed operation is permissible and agree on transfer permission, interlocking, protection and alarms. A standby pump is a separate machine. Agree on which faults it can cover and which common supplies, drives, sensors or controls can still stop both units. Ask for a single-line diagram showing the intended paths and identify any alternate path as a separately priced item. ABB motor-starting reference · Schneider Electric drive-bypass example · Grundfos twin-pump operating modes

Put standby, faults and restart in a sequence table

Use this as a worksheet for the owner, process designer and controls integrator. Record the permitted response and the person who approves it. The examples below are decisions to make, with no preset settings or restart permissions.

Put standby, faults and restart in a sequence table
State or eventDecision to record in the RFQWhat to observe at acceptance
Normal automatic demandWho issues the demand, how the lead pump is selected and what must be healthy before a startCommand and run feedback appear separately. The correct unit starts under an agreed simulated demand.
Lead pump fails to start or its drive tripsWhat proves a failed start and when a healthy standby with an available power path may take overSimulate missing run feedback and a drive trip separately. Verify the alarm and the agreed standby response.
Motor protection or shared process interlock tripsWhich trips inhibit the affected motor on every power path, which conditions inhibit both pumps and who can reset themVerify that neither a bypass request nor a standby request overrides the approved inhibit.
Demand rises with lead pump healthyWhether duty-assist is allowed, how assistance is requested and how it endsDemonstrate that a demand for assistance is handled as specified, independently of failover.
Feedback or communications is lostWhich inputs are essential, what local control remains available and which state is allowed on invalid dataSimulate the agreed signal failures. Verify alarms, the permitted operating state and its recovery conditions.
Utility or control power returnsWhich pumps remain stopped, which may restart, who authorises restart and what staggering is requiredSimulate power recovery under controlled test conditions. Verify restart inhibits and the agreed order.
A pump is isolated or in local modeWho has command authority, how availability is signalled and whether remote start is blockedConfirm mode indication, unavailable status and that the approved protection and interlocks remain effective.
Alternate drive path requested, if includedWho authorises transfer and whether the pump and process can run at line speedVerify indications, transfer permission and interlocking against the approved circuit and procedure.

Scroll the table to read all columns. Keyboard users can focus it and use the arrow keys.

Write down what counts as “running”. A contactor auxiliary contact or a drive running bit can indicate an electrical state. If the process needs proof of delivered flow or pressure, specify the separate feedback and who supplies the instrument. For the factory acceptance test (FAT), label inputs that will be simulated and reserve field proving for the agreed site acceptance test.

Put the same boundaries on every quotation

Put the same boundaries on every quotation
RFQ itemGive the supplierAsk the bidder to return
Pump and motor dutyPump tag list and curves, motor nameplates, supply, speed or fixed-speed duty, and starts or demand patternProposed arrangement per pump, equipment data, sizing assumptions and any deviations
Power circuit and installationSingle-line diagram, supply fault level, cable lengths, environment, mounting and terminal responsibilitiesScope for drives or starters, protection, disconnects, filters, ventilation, and any alternate path
Sequence and signalsCompleted state table, cause-and-effect or sequence narrative, and a point list with signal ownerControl architecture and I/O list distinguishing command, availability, run feedback, trip and reset
Local and remote operationMode and command priority, any supervisory system, communications requirements and control power arrangementHardware, HMI, programming and protocol deliverables, plus limits at the agreed terminals or network connection
Instruments, field works and testingResponsibility for motors, sensors, valves, field cables, installation, commissioning and site provingSeparate inclusions, exclusions and options, drawing and software deliverables, and FAT/SAT scope

Scroll the table to read all columns. Keyboard users can focus it and use the arrow keys.

Ask each bidder to price the same approved sequence and show changes as options. If the plant requires a common drive, dedicated drives, a line-power bypass or duty/standby changeover, ask the bidder to identify that arrangement explicitly. A controller or cabinet description alone does not define any of those circuits.

Match the scope to the cabinet family

FUBANG's product range includes the BQG2 VFD control cabinet for applications that require motor speed control, the RQG2 soft-starter cabinet for controlled starting, and the FBZG2 PLC control cabinet for project-specific automation. The actual drive or starter selection, control architecture, bypass arrangement, instruments, programming and site services depend on the approved scope. Start with the motor-control cabinet families and PLC cabinet section. For the upstream board and feeder scope, see the low-voltage switchboard procurement guide.

Public procurement documents illustrate why this scope matters. A closed Depok utility tender named a pump and VSD panel in one work item. A Jakarta project requested shop drawings, automatic and manual modes, level-based control, VSD starting and motor protection. These are examples of requirements defined by individual buyers. Use your own specification and approval process. Depok utility tender · Jakarta project technical specification