FBWGD supplies local secondary control and compatible operating mechanisms in ring-main units, compact substations and outdoor switching equipment. Select the unit by continuous demand and the duration of each operating pulse.

FBWGD equipment
FBWGD

Local DC Supply at the Switching Equipment

The compact unit combines AC/PT supply and battery backup for secondary control. It can serve protection and intelligent terminals, and operating mechanisms that fit its power and duty limits.

Check the available mounting space, terminal access and operating environment with the switchgear layout. Enclosure dimensions and installation details are confirmed for the selected unit.

Match Power to Its Duration

DutyListed power optionsCondition
Continuous output100 / 200 / 300 WSelect for sustained control and indication loads.
Short-duration battery output200 / 400 / 600 W20 seconds; select for the operating duty.
Maximum pulse outputUp to 1,500 W200 milliseconds, supplied by the battery.

These values describe different duties. The 1,500 W pulse rating is not a continuous rating. Confirm the required pulse, repetition rate and battery state for the actual mechanism.

AC / PT Input & DC Options

ItemSelection information
AC input176–265 VAC
PT input85–130 VAC; source capacity must be confirmed for the selected unit and duty.
Frequency50 Hz ±10%
DC outputs listed220 / 110 / 48 / 24 VDC; specify the required output when enquiring.

Confirm the present unit version for the selected voltage. Do not substitute a PT source solely on the basis of voltage: its available power and protective coordination also matter.

Battery, Supervision & Protection

The unit uses automatic battery charge/discharge management and supports supervision and alarms. Battery capacity and required autonomy are selected around the control load and operating sequence.

Confirm the supplied protective functions, alarm contacts or communication connection, mounting arrangement and wiring diagram for the unit. No enclosure protection rating or remote protocol is assumed from another DC product.

Selection Questions

Can FBWGD supply a switching motor continuously at 1,500 W?

No. The listed maximum 1,500 W is a 200 ms battery pulse. Continuous output options are 100, 200 and 300 W.

How should a PT source be specified?

Provide its voltage, available VA rating and the other connected loads. The required PT capacity is checked against the selected unit and operation sequence.

Discuss Your Configuration

Share the information you have. A complete specification is not required for an initial enquiry.

  • Required DC voltage and continuous watts.
  • Mechanism pulse power, duration and operating sequence.
  • Battery autonomy, AC/PT supply details and mounting space.

Ask for the available catalogue, drawings and technical documents for your equipment.

Browse DC & Station Power · All product families